Category |
Public Well |
Private Well |
|
Abandonment |
Fill within 30 days of excavation |
Must be filled, sealed, & plugged within 30 days of excavation or disuse |
|
|
|
To
be filled, sealed, & plugged by present owner of well or borehole |
|
|
|
Wells considered to be permanently abandoned when it has not been used for >
3 years. |
|
|
|
Wells considered to be temporarily abandoned when it has not been used for
>1 year and < 3 years |
|
|
|
|
|
Access Ports and Tubes |
No
standard specified |
No
standard specified |
|
|
|
|
|
Drilling Fluid |
Drilling fluids to be from an uncontaminated source or disinfected |
No
standard |
|
|
Dug, bored, or jetted wells are prohibited for all new public water systems |
No
standard |
|
|
Maintain tools & equipment in a sanitary manner |
No
standard |
|
|
|
|
|
Slab |
Slab to extend 2 ft. in all directions and slope away from casing |
|
|
|
Well must have a concrete slab with 6 in. thickness surrounding well casing |
|
|
|
|
|
|
Annular Space |
|
To
be grouted to prevent entrance of pollutants |
|
|
|
|
|
Base |
No
standard specified |
No
standard specified |
|
|
|
|
|
Caps |
No
standard specified |
No
standard specified |
|
|
|
|
|
Category |
Public
Well |
Private
Well |
|
Casing |
Must be new |
To
be new |
|
|
Outer casing to extend at least 5 ft. into first solid, unweathered or
impervious subsurface |
No |
|
|
|
Shall be steel, plastic, or concrete and meet nationally accepted standards
for well casing |
|
|
Shall have minimum length of 25 ft. from ground surface into water-bearing
crystalline rocks |
no |
|
|
No |
Shall not use sewer pipe |
|
|
To
extend at least 12 in. above concrete slab of floor |
|
|
|
To
have length of 50 ft. in a well excavated into sedimentary water-bearing
formations |
|
|
|
|
|
|
Joints |
To
be watertight and extend entire length of drilled wells |
To
be watertight entire casing length in drilled wells |
|
|
|
To
be watertight to the point of maximum drawdown in bored or driven wells |
|
|
|
|
|
Steel |
To
conform to ASTM A120 or A53 or to API 5L or 5LS |
|
|
|
|
|
|
Plastic |
Must be approved by Division |
|
|
|
Shall not extend to depth >300 ft. below ground surface |
|
|
|
To
meet ASTM Standard F480 |
|
|
|
|
|
|
Construction |
|
All wells to be curbed at surface by owner with watertight curbing of
concrete |
|
|
|
Curbing must be at least 4 in. thick and extend at least 2 ft. in all
directions from casing |
|
|
|
|
|
Cross Connections |
Conform to Standards of AWWA Manual 14 & EPA Cross-Connection Manual |
No
Standard Specified |
|
|
|
|
|
Category |
Public
Well |
Private
Well |
|
Disinfection |
After disinfection, well must be pumped until no trace of chlorine remains
in water |
Disinfect following construction, or repair before placing in service |
|
|
Disinfect pump & pumping equipment before they are serviced |
|
|
|
|
Minimum contact time of 2 hours before pumping of well |
|
|
Must occur in accordance with AWWA Standard C654 |
|
|
|
Must occur prior to pumping test with a chlorine solution under pressure |
|
|
|
Produce minimum chlorine residual of 50 ppm in 6 hours |
|
|
|
|
Well & equipment to be disinfected with chlorine so that 50 ppm of chlorine
is obtained |
|
|
|
|
|
Electrical Connections |
NSS |
NSS |
|
|
|
|
|
Fracturing |
NSS |
NSS |
|
|
|
|
|
Gravel |
|
Be
clean, disinfected, and free of organic matter |
|
|
To
be washed, free of organic matter, & composed well-rounded particles |
Consist of siliceous, well-rounded, smooth, uniform grain particles. |
|
|
|
|
|
Gravel/Sand Packed Wells |
NSS |
NSS |
|
|
|
|
|
Grout |
Cement grout protective casing entire length with a cement slurry |
|
|
|
Place under pressure from bottom of annular space up to earth's surface |
|
|
|
Slurry to not consist of >6 gal water to 1 cubic ft. of cement plus
additives |
|
|
|
Subsurface construction to cease for at least 24 hours after grouting |
|
|
|
|
To
be neat or sand-cement grout or other impervious material |
|
|
|
Wall thickness to not be <1.5 in. at any point |
|
|
|
|
|
Housing |
To
enclose water treatment equipment |
No
Standard Specified |
|
|
|
|
|
Identification |
No
Standard Specified |
No
Standard Specified |
|
|
|
|
|
Category |
Public
Well |
Private
Well |
|
Licensing |
Construction to be done by a licensed water well contractor in the State of
Georgia |
Must be a licensed water well contractor to construct wells |
|
|
|
May apply for a trainee license in order to complete 2 years of experience
under supervision |
|
|
|
May have to complete no more than 4 continuing education hours annually |
|
|
|
Must have 2 years of experience & pass an examination administered by the
council |
|
|
Owner must retain a Professional Engineer registered in Georgia to prepare
plans & specifications |
|
|
|
|
|
|
Location |
Do
not locate in floodplain unless measures have been taken to prevent
submergence of casing & equip |
|
|
|
Locate as far removed as possible from all open abandoned wells |
|
|
|
|
Locate as far removed from potential contaminants and in opposite direction
of ground-water flow |
|
|
Locate as far removed from potential contaminants and in opposite direction
of ground-water flow |
|
|
|
|
Wells must not be subject to flooding |
|
Sewer Line |
Sewer Line 10 ft |
Sewer Line 10 ft |
|
Cess Pool |
|
Cess Pool 150 ft |
|
Seepage Pit |
|
Seepage Pit 150 ft |
|
Septic Tank |
Septic Tank 50 ft |
Septic Tank 50 ft |
|
Septic Tank Field |
Septic Tank Absorption Field 100 ft |
Septic Tank Absorption Field 100 ft |
|
Barnyard |
|
Barnyard 100 ft |
|
|
|
|
|
Solid Waste Disposal Site |
1000 ft. and not in direction where ground water flow will be intercepted by
the well. |
|
|
|
|
|
|
Category |
Public
Well |
Private
Well |
|
Maintenance and Repair |
Nss |
NSS |
|
|
|
|
|
Permitting |
Must obtain permit from Director |
NSS |
|
|
|
|
|
Plumbness and Alignment |
NSS |
Installation & operation of pump not to be impaired |
|
|
|
|
|
Pumps |
Concrete block to extend at least 12 in. above concrete slab |
NSS |
|
|
Discharge Pipe to have raw water-sampling tap |
NSS |
|
|
For turbine pump installations, concrete block to support pump motor must be
constructed around casing |
NSS |
|
|
Outer casing to extend at least 1 in. above pump motor block |
|
|
|
Protect from unauthorized entry with enclosed shelter or fence |
|
|
|
Well head & pump base to be sealed & vented by screened riser pipe |
|
|
|
|
|
|
Screens |
Must be new |
|
|
|
|
Must withstand chemical and physical forces |
|
|
|
Permit optimum development of aquifer with minimum head loss |
|
|
Plastic screens to be approved by Division |
|
|
|
|
Prevent clogging or jamming |
|
|
|
|
|
Seals |
|
Individual wells- 10 ft |
|
|
|
Minimum depths below ground surface |
|
|
No
Standard Specified |
|
|
|
|
Nonpublic wells- 25 ft. in igneous or metamorphic rock |
|
|
|
Nonpublic wells- 50 ft. in sedimentary rock |
|
|
|
|
|
Testing |
NSS |
NSS |
|
|
|
|
|
Vents |
NSS |
NSS |